Legionella: is a DHW production temperature of 60°C necessary?

Recent research by WTCB has shown that lowering the domestic hot water production temperature to 45°C while keeping Legionella growth in a plumbing system under control through regular thermal shocks is far from straightforward. The current temperature requirements in ‘BBT Legionella’ (production at 60°C, with a minimum of 55°C on the return) were also tested and proved sufficiently safe to ensure hygienic water quality. It is therefore still recommended to follow these requirements, writes Bart Bleys (Head of the Water Technology Laboratory at WTCB), in collaboration with Karla Dinne (Head of the Microbiology and Microparticles Laboratory at WTCB).
Pressure on production temperatures
In recent years, the high production temperature of domestic hot water (DHW) has come under increasing pressure. As insulation standards rise and new buildings become more energy-efficient, DHW production accounts for an ever larger share of our total energy consumption. In addition, high production temperatures result in greater standing losses and are not optimal for all modern heating appliances. It is therefore hardly surprising that more energy-efficient DHW production solutions are being sought, with particular interest in lowering the production temperature. For this reason, WTCB launched a study in 2014 into energy-efficient options for Legionella control. The main priority throughout was that hygienic water quality must take precedence over any potential energy savings, important though these are.
WTCB test rig and results
The test rig in Limelette was built as part of the VIS Instal2020 project. It includes a 200-litre hot water cylinder, an insulated circulation pipe approximately 40 m long and two draw-off points, where previously defined draw-off profiles for a shower and a kitchen tap are applied. In this way, the installation provides a simple simulation of the DHW system in a household of 4 to 5 people. For the study, several sampling taps and a culture cylinder were also added, and the system was fully equipped with temperature and flow meters. The culture cylinder, containing bacteria from a real contaminated system, was connected only to initially contaminate the test rig. Once the system was contaminated, the cylinder was disconnected and the system supplied with fresh drinking water so that the response of the bacteria present to various temperature regimes could be monitored specifically.
45°C: 60°C
In the first phase of the study, DHW was produced at 45°C, with regular shocks at 60°C. The system was monitored weekly, and the heating regime was adjusted in stages in response to the results, starting with a weekly 30-minute temperature shock, with or without thermal flushing of the draw-off and sampling taps, and progressing to daily 60-minute shocks. Over the course of these weeks, the system also underwent several modifications to prevent Legionella growth: adding a destratification pump proved crucial to achieving an even temperature distribution in the cylinder and thus avoiding temperatures that were too low at the bottom of the tank. The expansion vessel, located on the cold side of the cylinder, was an important source of recontamination and therefore had to be removed. Despite the high frequency of thermal shocks and the additional measures, however, Legionella contamination was never brought under control during this test phase. Concentrations below 1000 CFU/l, as recommended by the Hoge Gezondheidsraad, were achieved only a few times, and immediately rose again after the thermal shock.
45°C: 65°C
An alternative regime was therefore proposed in the second phase. Production still took place at 45°C, but the thermal shocks were carried out at 65°C. The process again began with a weekly 30-minute shock, which was gradually extended. The first positive results were recorded when all draw-off and sampling taps were flushed for 30 minutes during a weekly shock, albeit with high water consumption and the associated practical implications. The next stage therefore focused on integrating thermal flushing of the draw-off points into the system’s normal use. The kitchen tap proved the most difficult factor, because it is normally used for very short draws. In the end, Legionella contamination in the test rig was kept below the prescribed 1000 CFU/l with a weekly 24-hour shock and a minimum draw-off of 150 seconds at every draw-off point.
BBT Legionella
For comparison, the regime prescribed by BBT (production at 60°C, with a minimum of 55°C on the return) was also applied to the test system. This brought Legionella contamination under control quickly and kept it there. In other words, the current BBT temperature requirements are safe.
Bart Bleys, Head of the Water Technology Laboratory at WTCB