Heat pump system | Sports hall in Gemert

Sportcentrum Molenbroek in Gemert has undergone an extensive renovation, from asbestos removal to replacement of the heating and hot water system. Renovation is the perfect opportunity to opt for more sustainable solutions. In this case, solar panels were installed on the roof, and a heat pump system was selected to heat the spaces and provide domestic hot water. Sports facilities typically do not have a continuous demand for hot water, but instead need large volumes over a short period at several times throughout the day.
Application
- Hot water
56 showers; 1,920 litres at 38°C, with a flow rate of 6 litres per minute for an average duration of 5 minutes.
- Heating
300 kW low-temperature heating, designed for a 45/35°C flow and return temperature.
Description
The sports centre consists of 2 large sports halls, a dojo, 8 changing rooms, a meeting room, a canteen and a number of ancillary spaces.
The 2 large outdoor units (Enevator Air Standard 340 kW) provide heating throughout the sports centre. The heating circuit is designed for a 45/35°C flow and return temperature. The units also provide hot water, which serves as the heat source for the Enevator Aqua Booster (indoor unit), which supplies domestic hot water at up to 78°C. This allows athletes to enjoy a comfortable shower after their activities.
We supplied the complete system. In addition to the heat pumps, this included a 1,500-litre ST storage tank and a bespoke buffer tank.
The system consists of the following products:
2 x AWHS 340 air-to-water heat pumps. Enevator Air Standard
1 x WWHB 45 water-to-water booster heat pump Enevator Aqua Booster
1 x ST 1500 storage tank
1 x SBT buffer tank used as a low-loss header, made to measure for this project
System schematic

Bespoke buffer tank
As we have our own Tankplant, we can make tanks and buffer vessels to measure. Specifically for the Sportcentrum Molenbroek project, we made a vessel with connections designed to meet the needs of this installation.
We first drew up the buffer vessel. Our CAD draughtsperson produced a detailed technical drawing for the specialists at what we call our Tankplant. This allows us to supply a perfectly fitting product with a short lead time.

Heat pump energy efficiency
The Enevator Air Premium heat pumps deliver water at temperatures of up to 63°C, making them suitable for a wide range of space-heating and domestic hot water applications. They can achieve COPs (coefficients of performance) of up to 4.64 and are part of a range comprising 9 different models, with capacities of up to 100.7 kW. These heat pumps operate at outdoor temperatures as low as -20°C.
Heat pumps
We believe that fossil fuels should be used responsibly and that sustainability matters. That is why our range includes heat pumps capable of meeting the hot water needs of medium-sized to large projects. Outputs range from 22 kW to 463 kW, providing very large volumes of hot water. The high temperature range, up to 78°C, makes our heat pump systems suitable not only for space heating but also for producing domestic hot water.
Need higher temperatures?
The Enevator Aqua Booster is used as a top-up heater when higher temperatures are required. This may be in a heat pump system such as the one at the sports hall in Gemert, but also where district heating is used or heat is recovered from an industrial process.

A.O. Smith heat pump systems
A.O. Smith has expertise in all technologies and is happy to advise on designing an effective hot water system. Every situation is different. The volume of hot water, the required temperature and peak loads all need to be considered when recommending the best system. In most cases, combining technologies, including heat pump technology, makes it possible to put together a system that is sustainable, reliable and financially viable. For example, a heat pump can be combined with a gas-fired or electric boiler to meet peak demand. Providing this kind of advice requires extensive calculations and knowledge of the different technologies. A.O. Smith has all this expertise in-house and is therefore ideally placed to provide sound advice on medium-sized to large heat pump installations.
A business enquiry for A.O. Smith BV? Get in touch
Who worked on it
Sportcentrum Molenbroek in Gemert-Bakel, renovation
- warmtepompsystemen
A.O. Smith
Keep following this
Get an email when a new story is published. No account needed.
- ProjectSportcentrum Molenbroek
- ThemeFossil-free heating and cooling
- SubjectHVAC
- CompanyA.O. Smith BV