Low temperatures demand high design standards

Text Christobal van LeeuwenImage Pexels en Vecteezy

Ontwerp op comfortgrenzen, niet op maximale oppervlaktetemperaturen.
Ontwerp op comfortgrenzen, niet op maximale oppervlaktetemperaturen.

Underfloor heating: comfort and efficiency depend on system control

Underfloor heating is no longer an additional comfort feature. In new-build projects, and increasingly in renovations too, it is the primary heat emitter. This makes sense: low flow temperatures are an ideal match for heat pumps and provide even heat distribution.

But low-temperature heating places high demands on the system. Treat underfloor heating as a standard product and sooner or later you will face comfort complaints or reduced efficiency. The difference lies in the design, hydraulic balancing and control strategy.

Design starts with heat loss

A professional design starts with a heat loss calculation for each room. Only then should pipe spacing, circuit lengths and water temperatures be determined. Not the other way round. The choice between primary heating, supplementary heating or combined heating and cooling determines the sizing. This should be based on a realistic, and thermally unfavourable, floor finish. Designing around a permanent tile floor is risky. If parquet or carpet is installed later, the required flow temperature will rise, directly affecting the efficiency of heat pumps and condensing boilers. Efficiency is determined at the design stage.

Pipe spacing and floor build-up are crucial

Pipe spacing is not an installation detail, but a comfort parameter. Excessive centre-to-centre spacing causes so-called temperature striping and insufficient heat output. Spacing pipes too closely increases material use and pump power without delivering a proportionate comfort benefit. In living and office spaces, around 30 cm is considered the upper limit. In bathrooms and comfort zones, pipes are laid closer together.

The floor build-up also affects system behaviour. Wet systems provide thermal mass and stability, but respond slowly. Dry and renovation systems respond more quickly, but require precise coordination between heat distribution, floor finish and control. Cutting channels into an existing screed is a practical option, provided the floor build-up is suitable and offers sufficient cover. The lighter the build-up, the greater the influence of control and floor finish on the final result.

Comfort has its limits

Underfloor heating provides radiant comfort, but within physical limits. Under EN 1264, a maximum floor surface temperature of 29 °C is generally applied in normally occupied rooms (at a room temperature of 20 °C). Higher temperatures increase the risk of discomfort and damage to floor finishes. Designing for the maximum temperature is treating the symptoms. Designing to comfort limits means thinking in terms of the system as a whole.

Zone control can improve comfort, but requires enough circuits per room and a control strategy suited to the system’s thermal inertia.

The R-value determines efficiency

The thermal resistance of the floor finish directly affects the required water temperature. In practice, a maximum R-value of around 0.15 m²K/W is often used as a guideline for homes. A higher R-value necessitates higher flow temperatures and reduces heat pump efficiency. With combined underfloor heating and cooling, higher resistance also limits cooling capacity. The choice of floor finish is therefore an important system design parameter.

Where efficiency is lost

Comfort complaints are rarely caused by the pipe itself. They are almost always the result of poor system settings, such as incorrect flow rates in individual circuits, an incorrectly set heating curve or mixing control, or a lack of hydraulic balancing.

For heat pumps, stable low-temperature operation is essential. Peak operation undermines efficiency. Zone control can improve comfort, but only if the hydraulic design and circuit layout are suited to it. Balancing is not a formality at handover, but part of the system design.

Cooling requires dew-point control

Underfloor heating is increasingly used for both heating and cooling. The EN 1264 standard covers both applications. With cooling, the risk shifts from comfort to condensation. Without dew-point monitoring, moisture can form on or within the floor structure. An adequate control and safety system is therefore essential. In well-insulated buildings, underfloor cooling can make a worthwhile contribution to summer comfort, but it is comfort cooling, not a full replacement for active air cooling. In many situations, additional ventilation or dehumidification is needed to enable safe cooling.

Compact plant rooms and legionella

In renovation and new-build projects, underfloor heating manifolds are often installed in compact plant rooms, sometimes alongside a heat pump and hot water cylinder. Under the right conditions, this does not lead to an increased risk of legionella.

The conditions are clear: flow temperatures below 35 °C, sufficient separation between cold and hot water pipes, and ventilation that keeps the room temperature under control. The layout of the plant room is therefore part of the integrated design.

It is the system, not the pipe

Underfloor heating is not a standard component, but an integrated system. Comfort and efficiency are not determined by the pipe in the floor, but by design choices, hydraulic balancing and the control strategy.

Anyone using low temperatures must have the whole system under control. Only then can comfort and efficiency truly be balanced.

‎‎

Question about this story? Ask your question

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeFossil-free heating and cooling
  • SubjectHeating
Share this article

Advertisement

Follow on Installatie & Bouw Vlaanderen

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.