One of the museum’s guiding principles is: Sustainable and fair: impact on people, not the environment. With this statement in mind, the museum began its renovation and refurbishment works. The project took 2.5 years in total, but the result is now there for all to see. Abby Museum has become an impressive and striking building. From the outside, its modern pyramid-like form is what stands out most. Once inside, its red colour and high ceilings make it even more impressive.
The museum comprises both old and new buildings. Alongside the renovation, the museum was also expanded with a new pavilion and underground exhibition spaces. The buildings had to be connected, which made the installation considerably more complex because of the large amount of pipework required.
The second challenge was climate control in the museum. A stable and reliable ambient temperature and humidity are essential to keeping the delicate art objects in optimal condition.


Hybrid 4-pipe heat pump system
A hybrid 4-pipe heat pump system was ultimately chosen. The Enevator Air Standard 4-pipe heat pump has a heating capacity of 185kW and a cooling capacity of 174kW. The advantage of a 4-pipe heat pump system is that its circuits operate independently, making it possible to heat or cool separately, or to cool and heat simultaneously.
In this project, the 4-pipe system provides both underfloor heating and cooling, and supplies the various climate zones with heat or cooling. This ensures that the museum always maintains the right temperature and humidity. Keeping humidity and temperature under control at a constant level is particularly important for the museum to preserve its art collection. This means that both heating and cooling are required throughout the year, making a 4-pipe system the ideal solution for redistributing energy efficiently.
The system also supplies the booster heat pump, which produces domestic hot water for the buildings. A condensing gas boiler is also integrated to provide additional heating on the coldest winter days.
A hybrid system was chosen deliberately. The 4-pipe system is designed to achieve a perfect balance between the heat extracted from and delivered to the building. This ensures sustainable and efficient climate control.


We installed:
- Enevator Air Standard AWHS 270 ACF/SLN/RV/4P heat pump
- SBT 2,000-litre buffer tank for cooling
- Enevator Aqua Booster WWHB 20
- Plate heat exchanger
Gas condensing boiler as backup
COP stands for Coefficient of Performance. It is the ratio of the thermal energy produced by the heat pump to the total electrical energy consumed by it. A heat pump’s efficiency decreases as outdoor temperatures fall, in other words, its COP drops. Depending on gas and electricity prices, there is a point at which it may be worthwhile to use a gas boiler alongside the heat pump, for example, when outdoor temperatures fall below 0 degrees. At extreme temperatures below -20 degrees, some heat pumps are better switched off to prevent freezing. A backup is then needed to guarantee 100% operation. In this case, a 100% operational guarantee was one of the museum’s requirements, ensuring that the art objects remain in good condition even during severe winters.
Would you like to learn more about the differences between 2-pipe and 4-pipe heat pump systems and how they are used? Request the guide here and receive it as a free download in your inbox.
Do you also have a climate control and/or domestic hot water project underway and need advice? Contact our expert Wim Ros.
Question about this story? Ask your question
Keep following this
Get an email when a new story is published. No account needed.
- ProjectMuseum Abby
- SubjectNews