Ventilation systems and COVID-19: some guidelines

What about HVAC systems during the coronavirus pandemic? Daikin, a market leader in climate control systems, provides information and clarification on several matters relating to the maintenance and operation of Air Handling Units in an environment with COVID-19.
The current COVID-19 pandemic raises many questions on almost every front. The HVAC sector must also be aware of some technical precautions that can be taken during the COVID-19 pandemic.
Ventilation remains essential
It is recommended that the supply air and extract ventilation rates be increased. The purpose of ventilation is to clean the air by diluting or displacing pollutants (air supply) and removing them (air extract). In general, it is assumed that more ventilation reduces the number of infections. REHVA, the Federation of European Heating, Ventilation and Air Conditioning Associations, provides some practical guidelines. It recommends extending operating hours and even running ventilation 24/7. The same applies to toilet extract systems, which should also run continuously. The maximum possible amount of outdoor air should be supplied, and the number of people in the room should be minimised. This increases the volume of air per person.
Where mechanical ventilation is not available, it is important to use window ventilation to ensure adequate airing.

Humidification and air conditioning have no practical effect
COVID-19 is fairly resistant to environmental changes and is only affected by a relative humidity above 80% and a temperature above 30°C. These conditions are not feasible or acceptable in buildings, not least because of thermal comfort. Humidification therefore does not offer a solution for preventing the transmission and spread of coronavirus.
Safe use of heat recovery sections
It is recommended that heat exchangers be switched off during this pandemic, as virus particles can leak from the extract air into the supply air. If leaks in the heat recovery sections are suspected, adjusting the pressure or using a bypass may be an option to prevent a situation in which higher pressure on the extract side causes leaks into the supply side.
Do not use recirculation
Virus particles in return air ducts can re-enter a building, so the recirculation dampers should be closed. If this causes problems with cooling or heating capacity, this should be accepted, as preventing infection and protecting public health are more important than ensuring thermal comfort.

No need to clean ducts or replace outdoor air filters
In terms of maintenance, duct cleaning appears to have practically no effect. Viruses attached to small particles will not easily enter ventilation ducts and will normally be carried away by the airflow. There is also no need to replace outdoor air filters. Although filters are intended to clean the air, their capture efficiency for virus particles is limited. A coronavirus particle is 80-160 nm in size, which is smaller than the capture range of fine filters (capture efficiency of 65-90% for PM1). Virus particles aggregate with larger particles that are already within the filters’ capture range. In the rare cases where outdoor air is contaminated with viruses, fine outdoor air filters provide reasonable protection against low concentrations and the possible spread of viruses in outdoor air. In terms of filter replacement, normal maintenance procedures can be followed. Clogged filters are not a source of infection in this context, but they can reduce the air supply, which has a negative effect on possible indoor infections. Filters should therefore be replaced in accordance with the normal procedure when pressure or time limits are exceeded.
For more detailed information, Daikin refers readers to the REHVA website and accompanying documents: https://www.rehva.eu/activities/covid-19-guidance
A business question for Daikin Europe? Get in touch
Companies in this story