Fabric ducting in HVAC: a practical case study at Colruyt’s distribution centre: hygiene, comfort and efficiency

A conversation with Lawrence Jacob (Prihoda) & Steven Vanhaverbeke (Beltherm)
Host: Kris Vandekerckhove
In this episode of the Installatie & Bouw podcast, we take a closer look at a real-world HVAC project at Colruyt’s distribution centre, where cheese is stored under strict temperature and hygiene conditions. Together with Lawrence Jacob (Prihoda) and Steven Vanhaverbeke (Beltherm/EEG Ventilation), we discuss the choice of fabric ducting as an alternative to conventional air ducts. Find out how this solution contributes to optimal air distribution, easy maintenance, energy efficiency and comfort in the food industry, and what technical and practical challenges it involves.

Een zakelijke vraag aan Linumgroup / Prihoda? Get in touch
Full transcript
All chapters (27)
- Introduction to the HVAC project in the food industry
- Introducing Prihoda and fabric ventilation
- Introducing Beltherm and its role in the project
- Challenges of air distribution in a humid environment
- Why choose fabric ducts instead of conventional solutions?
- Hygiene and maintenance of fabric ducts
- Working with Colruyt and the scale of the project
- How fabric ducts work and distribute air
- Flexibility in the shape of fabric ducts
- Condensation, draughts and air velocities
- Project delivery and on-site installation
- The installer’s role and experience on site
- Challenges with suspension and stability
- Subsequent adjustments and flexibility
- Advantages over conventional ductwork
- Colour and hygiene
- Misconceptions about fabric ducts
- Installers’ experience
- Service life and maintenance
- When to consider them in a project
- Applications in new-build and refurbishment projects
- End customer’s response
- The end customer’s role in the project
- Beltherm takeover
- Cooperation between partners
- New projects
- Closing the podcast
Introduction to the HVAC project in the food industry
Kris Vandekerckhove Welcome to the Installatie & Bouw podcast. This time, we’re taking a closer look at a real-world HVAC project in the food industry. Today, we’re talking about Colruyt’s distribution centre, where cheese is stored under strict temperature and hygiene conditions. In an environment like this, air distribution is obviously no minor detail. It is a crucial factor for production, quality and energy efficiency alike. For this project, Prihoda fabric ducts were chosen in collaboration with Beltherm. At first glance, perhaps a less conventional solution, but one that offers, and has offered, a number of technical advantages. Joining us today to tell us more about this specific project are Lawrence Jacob from Prihoda and Steven Vanhaverbeke from Beltherm, now EEG. But they’ll tell us more about that shortly. So, let’s start with introductions. First up, Lawrence from Prihoda.
Introducing Prihoda and fabric ventilation
Lawrence Jacob Good morning, I’m Lawrence. I’m an account manager at Prihoda. That means I take care of everything from project follow-up and the design stage through to completion and after-sales service for projects in which we supply fabric ducts. What does Prihoda do? We make fabric ducts, in other words fabric ventilation systems, for all HVAC applications: supply air, extract air, cooling, heating, general ventilation and air exchange. The possibilities are extensive.
Introducing Beltherm and its role in the project
Kris Vandekerckhove We’ll come back to that shortly, of course. Steven, who are you and what was your role here?
Steven Vanhaverbeke Originally, a colleague was following the project for me. I actually jumped in partway through. Diego Van Akker was following it initially. Then my boss took over for a while. After that, they asked me to take over the follow-up. So I got involved in the technical follow-up, selections and finishing. My role at Beltherm is as the person responsible for commissioning.
Read the full transcriptCollapse transcript24 more chapters
Challenges of air distribution in a humid environment
Kris Vandekerckhove Right. We’ll certainly come back to that in more detail. So, Prihoda fabric ducts were recently installed at Colruyt’s distribution centre, where all the cheese is stored. What challenges did the project present?
Lawrence Jacob I think that in applications like this, involving cheese, we always find that humidity levels are very high. So you need to take that into account. We also have ducts designed for these conditions. Of course, when humidity is high, the first thing people worry about is condensation. They think, ‘Oh no, won’t that be a problem?’ Our products are an ideal solution here, because we use permeable fabrics. Our ducts are therefore free from condensation and corrosion.
Why choose fabric ducts instead of conventional solutions?
Kris Vandekerckhove Right. Was that the reason why fabric ducts were chosen for this project instead of a more conventional solution? Or were there other reasons as well?
Lawrence Jacob There are many advantages. I wouldn’t say that was the only reason for choosing fabric ducts. Ease of installation, for example, and so on. But I expect it was indeed a decisive factor.
Hygiene and maintenance of fabric ducts
Kris Vandekerckhove I imagine hygiene is also important in this case. You can’t just take steel pipes down to wash them and put them back up. But I assume fabric ducts can be washed?
Lawrence Jacob That’s right. We also fit standard zips in the duct every five metres, making the ducts easy to remove and machine-wash. It depends on the type of fabric, but all the ducts used on this particular project were washable. That was also a requirement.
Working with Colruyt and the scale of the project
Kris Vandekerckhove So that was a requirement from the outset. Did Colruyt already know you, or how did they get in touch?
Lawrence Jacob We’ve worked with Colruyt several times over the years, mainly in its stores. But I think this was the first time we’d worked with them specifically on a project of this scale.
Kris Vandekerckhove Right, and what scale are we talking about?
Lawrence Jacob Steven, roughly how many ducts were there? Quite a lot.
Steven Vanhaverbeke Fabric ducts were used in all the spaces that needed cooling, even the fridges. That’s… I believe we had to install around 50 to 60 ducts.
Lawrence Jacob Yes, something like that.
Kris Vandekerckhove How many metres of fabric?
Lawrence Jacob I’d have to add it up, but it would be several hundred metres, if not close to 1,000 metres of ducting.
How fabric ducts work and distribute air
Kris Vandekerckhove Wow, right. So how do you make sure that air reaches the right place in a room in the right way? It comes out all over the duct, doesn’t it?
Lawrence Jacob We use design software that also lets us run simplified CFD simulations, which means we can work very precisely. The first things we need to calculate the system are the airflow rate and static pressure. From these, we can work out the air velocity at any given point. We can position the ducts in the space and use the software to see exactly how the air is distributed. We can also provide diagrams that clearly show the airflow.
Flexibility in the shape of fabric ducts
Kris Vandekerckhove Should I picture round ducts, or can you install them in other shapes too?
Lawrence Jacob In this case, for example, the ducts were semi-circular and fitted directly against the ceiling. They are essentially a circle split in two, with a flat top. We also have quarter-round ducts, segmented ducts and sector-shaped ducts, where you can choose the angle yourself, for example in a roof ridge, to get a very precise fit. The possibilities are extensive.
Condensation, draughts and air velocities
Kris Vandekerckhove The main things to watch out for in air distribution are condensation and draughts. How were these dealt with in this project? I assume there are people working in certain areas. Obviously, you don’t want air blowing down their necks all the time.
Lawrence Jacob We always distinguish between staff who are moving around and staff who are stationary. By moving staff, we mean people who are constantly on the move. For example, forklift trucks operating in a warehouse. Then there are workstations and machines where people stand all the time, or people sitting at their desks. Those require a different approach. In office environments, we aim for air velocities of between 2 and 5 metres per second. In industrial spaces, so to speak, or spaces where more staff are moving around, the velocity can be a little higher. It is often in the range of 7 to 7.5 metres per second.
Project delivery and on-site installation
Kris Vandekerckhove Let’s move on to the installation and commissioning, Steven. Could you take us through the collaboration between Prihoda and Beltherm on this project, from design to installation?
Steven Vanhaverbeke When I started on the project, there was a small problem with the passage through to the rooms. It had been provided by the isokap. It hadn’t actually been finished to make it airtight, so we had to extend the ducts until they reached the room. We then connected the zip at the top and fitted a T-piece, before carrying on from there. As for the installation, you hang two aluminium rails and slide the ducts into them. They were simply zipped together. That was it. The hardest part was hanging the rails at the right distance apart.
The installer’s role and experience on site
Kris Vandekerckhove Were you involved from the start of the project, or was it more a case of being handed the job and told what to do?
Steven Vanhaverbeke We were the installation contractors.
Kris Vandekerckhove Steven, you’re used to working with different systems. What’s the difference on site? In terms of weight, speed of installation and perhaps ease of handling?
Steven Vanhaverbeke Working with fabric ducts in the plant room is very difficult, for example. Particularly because the temperatures are different there, and because of the need to insulate them. I don’t know whether insulated TB1-class fabric ducts are available?
Lawrence Jacob We have insulated ducts. These have a layer of rockwool fitted on the inside.
Steven Vanhaverbeke Would that be suitable for hygiene requirements?
Lawrence Jacob For food applications, for example, yes. Everything used in food applications.
Steven Vanhaverbeke For example, timber extraction is also very difficult, because it operates under negative pressure. A duct without a shape is very difficult to install in practice, unless it has a frame. We’ve used that once, probably for cleaning as well. But as long as it is isothermal, it isn’t a problem.
Steven Vanhaverbeke And in terms of weight, they don’t weigh much. Aluminium or stainless-steel ducts are much heavier. But we can only use fabric ducts at the terminal points, instead of grilles.
Challenges with suspension and stability
Kris Vandekerckhove You said the main challenge was the rails, in other words, the suspension. Why was that?
Steven Vanhaverbeke They have to hang perfectly parallel. The first time, it was nerve-racking to see whether the T-piece would move too much. If the velocity is too high, the ducts start vibrating.
Subsequent adjustments and flexibility
Kris Vandekerckhove I understand that this project was actually carried out in two parts. The installation was completed, but it turned out there was another challenge and an adjustment had to be made afterwards. What exactly was that?
Steven Vanhaverbeke: We had already dismantled the ducts where the T-pieces were difficult to reach because we could not connect to the pipe, to the connection, while the fabric ducts were in the way. We dismantled those sections and Lawrence arranged for them to be transported to a sewing workshop. They added extra zips there to make it easier to connect them.
Lawrence Jacob Yes, to make the connections accessible. They were difficult to reach before because the rails were in the way too. Now it is simply a matter of opening the zip, and you can connect to them straight away.
Advantages over conventional ductwork
Kris Vandekerckhove: That seems like an undeniable advantage to me.
Lawrence Jacob Yes, that is something that can be typical of this kind of work. With any modification after installation, the question is always whether it is possible. But we always try to work with our customers to find a solution. In this case, it was possible. Of course, given the scale of the project, the sewing workshop had quite a bit of work to do, and it took some time. But we are pleased that we were able to see it through and that everything is now working well.
Kris Vandekerckhove: If you came across the same issue with steel or stainless steel pipes, it would be almost impossible to resolve without starting all over again.
Lawrence Jacob That is indeed one of the advantages: the ducts can be removed and transported quite easily. For example, we have just been talking about their weight. Another advantage is that fabric ducts take up much less space than pipes when being transported to site.
Colour and hygiene
Kris Vandekerckhove: Does it say Colruyt everywhere?
Lawrence Jacob We would have been happy to do that if they had asked, but it was not needed here. The ducts are simply a neutral colour. In the food industry, blue is often used because there are no blue food ingredients. So if there is any contamination, you can spot it straight away. That is why we made everything blue.
Misconceptions about fabric ducts
Kris Vandekerckhove: Are there still any misconceptions about fabric ducts in the market, do you think, Lawrence? Among end customers?
Lawrence Jacob I suspect many end customers do not really know what fabric ducts are, and their first reaction may be to see them as inferior or cheaper. Yet they allow you to be much more precise with air distribution. We offer a 20-year guarantee on our fabric, so the quality is certainly there. I think our main challenge is that they are still unfamiliar, and what is unfamiliar is often viewed with suspicion. We see this especially among smaller companies, which tend to be more conservative. I think that is the main challenge. Technically, I believe we can meet a great many requirements.
Installers’ experience
Kris Vandekerckhove: Technically speaking, are there still any misconceptions among installers about fabric ducts compared with conventional solutions, Steven?
Steven Vanhaverbeke: It depends a bit on what the customer wants. We have used them extensively in cinemas. In the past, air was supplied from below the screen, which caused more draughts. We have now started supplying air from the corners, using quarter-circle fabric ducts. The throw can be determined using the nozzles on the fabric ducts. As a terminal unit with a constant airflow rate, it is a very good solution for people’s comfort, especially when they are standing still underneath. For example, I have a project in kitchens from ten years ago where first-generation fabric ducts are still installed, and they work perfectly.
Service life and maintenance
Kris Vandekerckhove: So they still work perfectly after ten years?
Steven Vanhaverbeke: Exactly. That was the fabric duct I saw installed. It was a slightly different model, but it was still intact.
Lawrence Jacob There is a reason we offer a 20-year guarantee on the fabric. It is certainly high quality, provided it is properly maintained. It depends on the application. It does not need to be washed every month, certainly not. I believe the guideline is once every four to five years. Food industry applications sometimes have stricter requirements, but it all depends on the application.
When to consider them in a project
Kris Vandekerckhove: If an installer, consultancy or client is listening to this podcast, at what point should they consider fabric ducts?
Lawrence Jacob I think from the design stage onwards. That way, you can plan for them. We are often already specified in the tender documents. I visit a lot of consultancies to make sure they know about us and consider us in their designs.
Applications in new-build and refurbishment projects
Kris Vandekerckhove: Are fabric ducts mainly of interest in new-build projects, or are they also suitable for refurbishment?
Lawrence Jacob Both. In principle, they can be used anywhere. Whether it is an office or, as Steven mentioned earlier, a cinema, everything is calculated and made to measure, so we can always adapt to the specific situation.
End customer’s response
Kris Vandekerckhove: How did the end customers, Mr and Mrs Colruyt, respond?
Lawrence Jacob I have not heard from Mr Colruyt himself, but I assume they were happy with the result. We also contacted them afterwards to ask whether we could feature the project in the podcast, because we thought it was such a great project and a major challenge in terms of scale too. They had no problem with that, so I assume they were happy with it.
The end customer’s role in the project
Kris Vandekerckhove: Were they actively involved throughout the project, or only at the beginning?
Lawrence Jacob It is much the same as with most projects. The end customer approaches a consultancy. In Colruyt’s case, that is its in-house design department. They specify the requirements, after which various installation companies are considered. Beltherm then contacted us to develop the fabric ducting solution. That is generally how projects on this scale work.
Beltherm takeover
Kris Vandekerckhove What is happening with Beltherm? You have a new name now. What is the story?
Steven Vanhaverbeke: We were recently acquired by EEG. We are now called EEG Ventilation. We are part of a large group that can handle everything from hospitals and schools to HVAC, plumbing and refrigeration. We deliver complete projects as well as multi-technical projects. We also have our own digital building solution for controls.
Cooperation between partners
Kris Vandekerckhove Is Lawrence on the phone to you every week now?
Lawrence Jacob Every week is putting it strongly, but we do speak regularly. We are also working on a number of projects together now.
New projects
Kris Vandekerckhove Can you tell us anything about them?
Lawrence Jacob For example, the VRT studios we briefly mentioned. We are proposing an atypical solution there. We are still at the quotation stage, so I cannot say too much about it yet.
Kris Vandekerckhove That sounds unusual, especially from an acoustic point of view.
Lawrence Jacob Indeed. Sound is important there, and fabric ducts absorb sound rather than transmitting it, unlike metal ducts.
Closing the podcast
Kris Vandekerckhove That is an ideal note to end on. Thank you, Steven, and thank you, Lawrence, for this illuminating explanation of the project.
Steven Vanhaverbeke: Thank you.
Lawrence Jacob Thank you.
Kris Vandekerckhove Thank you for listening to this podcast about the project at Colruyt. We have seen how a considered choice of air distribution, such as fabric ducts, can have a major impact on hygiene, comfort and efficiency in a critical environment such as the food industry. Thank you to our guests, Lawrence Jacob from Prihoda and Steven Vanhaverbeke from Beltherm, now EEG. For more insights like these, follow us on your favourite podcast platform or via Installatie & Bouw. Thank you for listening, and see you in the next episode.
Companies in this story
Keep following this
Get an email when a new story is published. No account needed.
- ThemeHealthy air and summer comfort
- SubjectHVAC
- CompanyLinumgroup / Prihoda