What are the key changes in the new AREI from 1 June 2023, and what impact will they have?

What are the key changes in the new AREI from 1 June 2023, and what impact will they have?

The AREI, the General Regulations on Electrical Installations, also known as the ‘electrical inspection’, was amended again by Royal Decree on 5 March 2023. The changes have applied since 1 June 2023, and include several important points to note.   

Tom Cauwelier, Teamlead Building at Vinçotte, and Timothy de Coninck, Energy Distribution Specialist at Rexel Belgium, discuss the new AREI in the latest ‘Rexel Talks’ podcast. 

The new, amended legislation follows relatively quickly after the previous version (from 2020), partly as a result of the technical evolution of electrical installations. The AREI’s aim remains, of course, to ensure safety, and the regulations apply to both new domestic installations and existing ones. A distinction is made between old existing installations and installations covered by the previous AREI.  

Another important point: a number of terms and definitions have been clarified or updated, introducing new terminology.  

  • Socket outlets are now called ‘contact outlets’ 
  • Automatic switches or ‘circuit breakers’ are now called ‘power circuit breakers
  • Residual current device is replaced by residual current protective device 

The latest AREI therefore has an impact across the board: from clearer definitions and more precise terminology to symbols on diagrams and practical applications on site.  

1. New domestic electrical installations  

It was already mandatory to connect fixed electrical appliances downstream of a 30 mA, to use the term one last time, residual current device. From now on, circuits supplying lighting circuits and socket outlets for portable electrical appliances are subject to the same requirement.  

The biggest change for electricians, then, is that they may need to add a 30 mA residual current protective device. This provides additional protection for everything supplying non-fixed appliances. It protects people against indirect contact and fire hazards, and also provides an extra safeguard against direct contact.   

Will distribution boards therefore become larger? In some cases, yes. The number of circuits is limited to 8 per additional 30 mA residual current protective device, so it is entirely possible that a few additional devices will be needed.   

Extra attention to the single-line diagram and site plan 

New symbols are being introduced in the single-line diagrams and site plans for domestic installations. New robotics and home automation, as well as developments in power sources, make an update necessary. Installers also have more freedom when drawing up diagrams and plans, as they may define a symbol themselves in the legend if it is not yet included in the AREI, and then refer to it.  

The formal requirements for the diagrams and plans accompanying every new domestic electrical installation, or every major alteration or extension to an existing domestic electrical installation, have also changed. For example, the owner no longer needs to sign them, but a duplicate is required. 

Our experts discuss this in detail in the podcast.

From 1 June 2023, the common areas of a residential complex are no longer considered ‘domestic installations’. As a result, the periodic inspection interval is 5 years instead of 25 years. 

2. Old existing domestic electrical installations dating from before 1/10/1981  

A number of derogations and exemptions were previously provided for these old domestic electrical installations. Examples include socket outlets without an earth pin or without child protection. From 1 June, these derogations are no longer in force and are effectively prohibited.  

Old domestic electrical installations must therefore also be fitted with the correct contact outlets, downstream of, once again, a 30 mA residual current protective device. The device installed in these old installations must also be type A. Previously, type AC devices could remain in service, but this is no longer permitted. Where a major alteration or extension is made to an old domestic electrical installation, the residual current protective device at the start of the installation may therefore need to be replaced with a sealable type A device. In addition, only screw-type fuses or circuit breakers with calibration elements are permitted.  

A practical change with a significant impact: unlike before, the bathroom, like the dishwasher, tumble dryer and washing machine, must always be connected downstream of an additional 30 mA residual current protective device. The main residual current protective device must also be sealable. 

The conclusion? A whole range of new safety measures apply to existing domestic electrical installations. What used to be covered by a ‘derogation’ has effectively disappeared.  


3. Existing domestic electrical installations that comply with the old AREI (up to 1987) 

The safety level here was already relatively high, so the impact is limited. The main changes are that type AC residual current devices are prohibited and that a residual current protective device must always be sealable.  

When new circuits are added to old or existing installations, portable appliances or lighting circuits must always be connected downstream of a 30 mA residual current protective device.  

If a residual current protective device is already installed, always count the circuits, because once there are more than 8 circuits, an additional 30 mA residual current protective device must be installed.  

What does the AREI say about secondary cabling?  

The AREI requirements for low-voltage and very-low-voltage electrical installations also apply to all cables used for communications and information technology. 

The CPR rules on the choice of cabling, IT wiring and communications remain unchanged. Only the role of the inspection body responsible for carrying out the electrical inspection has been clarified and made less open to interpretation.   

If the distance between this secondary cabling and the electrical wiring is less than 20 mm, the inspection body responsible for carrying out the electrical inspection must include it in its inspection and ensure that the presence of this cabling, IT and communications lines does not affect the overall safety of the electrical installation.  

***  

Have questions about the new AREI? Contact our experts or listen to the Rexel Talks episode first. It is sure to make things clearer, and we will then be on hand to help you dot the i’s and cross the t’s.  

Een zakelijke vraag aan Rexel Belgium? Get in touch

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • SubjectElectrical
  • CompanyRexel Belgium
Share this article

Follow on Installatie & Bouw Vlaanderen

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.