Since coronavirus first arrived in our country around a year ago, ventilation has been a hot topic.

Mechanical ventilation is recommended, especially when low outdoor temperatures make it impossible to keep a window open continuously. In systems with a heat recovery wheel, it is also important to use a purge sector. This helps prevent aerosols or virus particles from entering the fresh air stream. 

Controlled vs uncontrolled recirculation 

Controlled recirculation means that extract air is reused and supplied again to a particular space. This saves on heating or cooling. However, controlled recirculation is currently prohibited. During the coronavirus pandemic, 100% fresh air must be supplied. 

Uncontrolled recirculation occurs when extract air, which is contaminated, leaks into the supply air stream. Such leakage occurs when the ventilation system is unbalanced, when the air handling unit has not been assembled correctly, or when the heat exchanger is not properly sealed between the extract and supply air streams. Because of its design, sealing is more critical for heat recovery wheels than for counterflow heat exchangers. 

Counterflow heat exchanger and heat recovery wheel 

In a counterflow heat exchanger, the two air streams are separated by stationary plates made of highly thermally conductive material. A heat recovery wheel, by contrast, stores heat and moisture through accumulation as its rotor turns, using small openings. This creates a higher risk of leakage and uncontrolled recirculation. For this reason, REHVA (the European umbrella association for HVAC) advised checking all air handling units and, where there may be a risk of leakage, shutting the unit down for as long as coronavirus remains in the country. 

Purge sectors make heat recovery wheels just as airtight 

Komfovent air handling units with a heat recovery wheel fall into a different category. A Komfovent air handling unit with a heat recovery wheel is just as airtight as the version with a counterflow heat exchanger. Special brushes gently press against the wheel, improving the seal between the two air streams. These air handling units also have a heat recovery wheel with a purge sector, which greatly reduces leakage. 

In a ventilation system without a purge sector, air rotates with the wheel, meaning that extract air does enter the fresh air stream. As a result, a tiny proportion of the extract air enters the fresh air stream (for Komfovent, this amounts to 1 in 100 particles). Before the coronavirus pandemic, that 1% was negligible, but this portion may now contain aerosols, so leakage is best avoided. 

A purge sector prevents contaminated air from being carried back into the fresh air stream. This ingenious sector uses a small amount of fresh air to blow the extract air carried by the wheel out of the unit and outdoors. The purge sector thus removes 99.9% of contaminated air, allowing us to say with confidence that no aerosols or virus particles enter the fresh air stream. However, proper installation and a correct balance between the air streams are essential. 

Question about this story? Ask your question

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeHealthy air and summer comfort
  • SubjectHVAC
Share this article

Follow on Installatie & Bouw Vlaanderen

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.