Energy-efficient plant room at town hall thanks to gas heat pumps

In a world that is becoming increasingly sustainable, local authorities cannot afford to be left behind. Steenokkerzeel is also working to make its buildings more efficient and reduce CO2 emissions. With this goal in mind, Fluvius set about renovating the plant room at the town hall.
Steenokkerzeel regularly works with Fluvius on energy-efficiency renovations across its municipal property portfolio. “Fluvius handles all the practical aspects, from the study and tendering process through to implementation and handover,” says Patrick Martens of Fluvius. Tackling the town hall’s heating system was a fairly complex project, Martens says: “The building is heated and cooled by chilled beams. It had two boilers and a cooling system. However, the old boilers were faulty: the smaller boilers were leaking and the large atmospheric boiler was experiencing technical problems.”
Two gas heat pumps in cascade
Fluvius set out the various technologies side by side in a feasibility study. Costs were weighed against CO2 savings, and the project scope was defined. The final choice was two gas heat pumps in cascade, with a condensing boiler as backup. The municipality is eligible for an attractive grant for installing a gas heat pump. Following a competitive tender, Fluvius selected heat pumps from ClimaWays. Patrick Martens: “When choosing manufacturers, we look beyond simply supplying the equipment: the products must be impeccable in quality, and manufacturers must also help us find the right system solution. That is the only way we can guarantee a good end product.”

The refurbished plant room improves the efficiency of Steenokkerzeel town hall.
Fluvius encountered a few challenges during implementation, Martens explains. “To achieve an acceptable efficiency from a gas heat pump, the temperatures in the heating circuits had to be reduced from 75 °C to a maximum of 60 °C at an outdoor temperature of 10 °C. In addition, chilled beams operate with a very low ΔT. A high water flow rate is needed to deliver the required output at a low operating temperature. We therefore measured and reset the flow rates in all the heating circuits.” Fluvius also had to optimise the airflow through the chilled beams, which required modifications to the air distribution system. “There were also some comfort complaints in the building. To address these, we had to adjust the control sequence for all the heating circuits,” says Martens.
High efficiency
Two ROBUR PRO GAHP-A S1 air-to-water gas absorption heat pumps from ClimaWays proved to be a suitable solution. Martens says: “The advantage of this technology is that the system continues to deliver very good efficiency at higher temperatures. This is quite different from an electric heat pump, whose efficiency drops off almost entirely at temperatures above 48 °C. That makes a gas heat pump of this kind a much more attractive option for a renovation project.”