The importance of heating water quality in 2022

Voor grotere installaties wordt er vaker overgegaan tot een wateranalyse in het labo.
Voor grotere installaties wordt er vaker overgegaan tot een wateranalyse in het labo.

Measuring the key parameters of heating water quality is becoming an increasingly important part of the correct procedure for filling and commissioning a heating system. Measuring and understanding the results are crucial to taking the right precautions. Fernox, a leading water treatment specialist since its foundation in 1964, provides installers with essential advice and targeted solutions.

In July 2021, Technical Information Note 278, ‘Hot water heating systems: recommendations for preventing deposits and corrosion’, was published by the WTCB (Scientific and Technical Centre for the Construction Industry). A key starting point is the quality of the filling water, with the main parameters being pH (acidity), hardness (the amount of dissolved limescale), clarity and purity (turbidity). The conductivity of the heating water and the concentration of additives, such as pH buffers and corrosion inhibitors, should also be measured.

This new Technical Information Note brings new responsibilities for the installer. The quality of the filling water must be determined. Ten weeks after commissioning, the quality of the heating water must also be assessed if no chemical water treatment has been applied. This can be done on site using test kits or measuring equipment. Test kits have the advantage of being easy to use, for example pH test strips. However, they only give an indication and may not provide enough detail. Greater accuracy can be achieved with digital probes. The downside is that they are more expensive and must also be calibrated periodically, which is not always straightforward. 

Laboratory analysis

For larger systems, water is increasingly being sent to a laboratory for analysis. For around 50 euros, Fernox analyses 14 parameters that are important for the quality of filling and heating water. In accordance with Technical Information Note 278, the analysis report is then added to the heating system logbook. 

Specifications are also increasingly focusing on water quality, with references to NBN EN 12828 or pH buffering in accordance with NBN 14868. This trend is also supported by most boiler manufacturers, which offer a service at the commissioning of heat generators that includes measuring water quality. 

Measuring water quality does not, of course, mean that good practice in the installation, commissioning, management and maintenance of a good heating system can be ignored. But neglecting heating water quality from the design and commissioning stages onwards has already caused a great deal of damage and many problems. By providing the right tools, including test kits, digital probes, laboratory water analyses and water treatment, Fernox helps to prevent this.     

Een zakelijke vraag aan Fernox? Get in touch

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • SubjectYearbook
  • CompanyFernox
Share this article

Follow on Installatie & Bouw Vlaanderen

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.