Prevent corrosion and contamination and keep your systems in top condition

The number of thermal energy storage systems in our country is rising rapidly. This is hardly surprising, as they can ensure a comfortable indoor climate in every season when combined with low-temperature heat emitters, while using minimal energy. The key is to treat the system water correctly. Mario van Gorsel, director of KOREX Benelux, explains how.
“As temperatures are lowered in heating systems and raised in chilled-water systems, corrosion problems are increasing rapidly, even in relatively new installations. What’s more, dirt and sludge regularly find their way into closed systems during installation. This can include dust, welding spatter or construction debris, which, together with released limescale particles, can cause significant losses in efficiency and comfort, as well as faults and breakdowns.” To protect valves, shut-off valves, pumps and other advanced system components, KOREX Benelux is receiving an increasing number of enquiries about filtration, including side-stream filtration. The company also offers efficient water treatment for closed systems, for which the VUL-SEP® filter and softening unit and AIR-SEP® pressure maintenance units are ideally suited.

“Before a system is commissioned, we can already remove dust, welding spatter and construction debris from the system water,” says Van Gorsel. “The water is then softened in accordance with the German VDI 2035 standard, which stipulates that the water in closed circuits must be colourless and odourless, free of sediment and have a conductivity of ≤ 1,500 μS, depending on the size of the system. To achieve this, a VUL-SEP® is temporarily installed in the system to filter particles down to 50 microns from the system water. An ultra-powerful magnet collects the dirt particles in the unit and holds them in a ‘dirt zone’, while a water softener ensures that only soft water at 3°dH is added to the system.”
After a few days or weeks, the VUL-SEP® is replaced by an AIR-SEP®, which consists of an expansion vessel with an inlet valve, degassing valve, automatic top-up unit and pressure maintenance pump. “The pressure maintenance pump continuously draws 5 to 20 litres from the system and returns it to the AIR-SEP® vessel through the inlet valve. Here, the pressure is reduced to a vacuum pressure of -0.3 to -0.5 bar. Our patented vacuum technology reduces the air content by 28 to 40 mg/litre compared with the system water. This raises the pH value, keeps the protective oxide layers in the system intact and prevents air and dirt from being separated out. The result is optimal comfort, even higher efficiency, fewer faults and a significantly longer service life for low-temperature systems.”
Question about this story? Ask your question
Keep following this
Get an email when a new story is published. No account needed.
- SubjectYearbook