The importance of good system water quality in heating and cooling systems

Text Wouter PolspoelImage Louwers Mediagroep

V.l.n.r.: Yves De Meuter, Pieterjan Spyns, Wouter Polspoel, Vincent Vancaeyzeele en Yves Desplenter tijdens het rondetafelgesprek.
V.l.n.r.: Yves De Meuter, Pieterjan Spyns, Wouter Polspoel, Vincent Vancaeyzeele en Yves Desplenter tijdens het rondetafelgesprek.

System water quality has a major impact on the efficiency, reliability and service life of heating and cooling systems. Yet it rarely receives the attention it deserves. Installatie & Bouw therefore brought together four experts to shed light on the subject. What happens when oxygen, limescale or contaminants enter a system? Why do some systems fail after just a few months, while others run trouble-free for years? And who is responsible when things go wrong? These are just some of the questions they answered. The round-table discussion leaves little room for doubt: underestimate the importance of system water quality, and sooner or later you will pay the price.

Participants:

  • Vincent Vancaeyzeele: technology & innovation team manager at Techlink
  • Yves Desplenter, sales director at Fernox Pieterjan Spyns, owner of PJS Installatietechnieken
  • Yves De Meuter: quality manager at Vaillant Group
  • Moderator: Wouter Polspoel (content agency Palindroom), editor-in-chief of Installatie & Bouw België

Good afternoon, gentlemen. Let’s start by clarifying something. When we talk about system water quality in heating and cooling systems, what water are we referring to?

Yves Desplenter: “We mean the water circulating in the system. Clear water is the benchmark. As soon as you see discolouration, yellow, brown or black, you know contamination is occurring. Black water is sometimes described as ‘dead water’, with no oxygen or life in it, but that is not true. Corrosion can continue perfectly well without any further change in colour.”

Which physical, chemical and biological processes cause poor water quality in heating and cooling systems?

Yves De Meuter: “Oxygen is the main culprit. If it gets into the heating or cooling system, it triggers corrosion in metal components. This is virtually impossible to avoid: topping up, microleaks and oxygen diffusion through plastic pipes (oxygen from the surrounding air migrates through the plastic pipe into the system water, not through leaks, but through the material itself, ed.): all of these introduce small amounts of oxygen into the system.

Rust forms in oxygen-rich areas, while magnetite, a fine black sludge, develops in parts of the system with little oxygen. Limescale can also build up on pipe walls. Rust, magnetite and limescale can all break loose and circulate with the system water, causing blockages, wear and reduced efficiency.”

Pieterjan Spyns: “Good water quality is crucial in heating and cooling systems, but you must consider it in the context of the system design. For example, you can fill a new system with demineralised water, which contains no salts, minerals or dissolved gases that could trigger corrosion, limescale build-up and sludge formation in the system. But if you then introduce steel into the system, as often happens because it is cheaper than copper, you can still create problems.”

Yves De Meuter: “I completely agree with Pieterjan. The expansion vessel must also be considered as part of the system design. Its size needs to be carefully calculated and it must have the correct pre-charge pressure. Those factors largely determine whether there will be ongoing oxygen ingress.”

Yves Desplenter: “The type of system, large or small, new or existing, the type of heat emitter, the type of heat generator … and the temperature of the system water also play a part.”

Pieterjan Spyns: “The main problem is that people often respond incorrectly to contaminated system water. They flush it with water and top it up again. But that introduces more oxygen and only makes the problem worse.”

Yves De Meuter: “We have seen installers fill a heating or cooling system with well water at start-up because mains water was not available. It may seem like a practical solution, but you have no idea what you are introducing: iron, bacteria, minerals … You are effectively starting out with a contaminated system.”

Vincent Vancaeyzeele.

Are these problems caused by poor design, inadequate commissioning or insufficient maintenance?

Yves De Meuter: “It starts with the design. The system must be designed to minimise the risk of system water becoming contaminated. If you are renovating a heating or cooling system, you must always treat the water already circulating in it first. Proper commissioning is also important, of course. All of this costs money, and in the end, when a new or upgraded heating or cooling system is quoted, the bottom-line figures are often what matter most to the end user.”

Pieterjan Spyns: “Timely maintenance is important too, and it needs to be done properly. Guidelines for preventing contamination, corrosion and efficiency losses in heating and cooling systems are set out in Technical Information Sheet 278 from Buildwise. But hardly anyone knows about them in practice. I have never even known an architect to refer to them.”

Vincent Vancaeyzeele: “You said it yourself: they are guidelines, not laws. Even so, I find it surprising that so few people know about them. They are used as a reference in disputes over problems with heating and cooling systems. As an installer, you need to be on firm ground if you choose to depart from them. But I think the consensus is clear: problems are rarely caused by a single mistake. They are almost always the result of a combination of poor design, substandard installation and inadequate follow-up.”

Pieterjan Spyns: “Boilers must, incidentally, be serviced every two years by law. But responsibility for this lies with the end user, and there is no real check on compliance with the law.”

How quickly do problems arise when water quality in a heating or cooling system is poor? Are we talking about gradual degradation, or can systems lose performance quickly?

Yves Desplenter: “It depends very much on the situation. It can take longer for problems to arise in new systems, but that is no guarantee. Poor air venting, for example, can cause problems quickly.”

Vincent Vancaeyzeele: “We often see what is known as a bathtub curve: lots of problems at the beginning, then a period when everything seems to stabilise after intervention, followed by major problems after five to ten years, having accumulated in the background all that time.”

What are the practical consequences of poor water quality in heating and cooling systems?

Vincent Vancaeyzeele: “It can lead to all sorts of problems: blockages in pipes or radiators, pump failures, damaged heat exchangers …”

Yves De Meuter: “Often, problems first show up in the appliance itself, because that is where tolerances are tightest, the passages are narrowest and flow is most critical. But that does not mean the problem originates there. The appliance is often simply the first place where the effects become visible.”

Pieterjan Spyns: “In extreme cases, a heat exchanger can simply develop a leak because the water is too acidic. Water then mixes with the refrigerant and the system is a total loss.”

The announced federal tax shift and rising gas prices following the US and Israeli attack on Iran will undoubtedly boost the heat pump market. So we would like to focus on heat pumps for a little longer. Specifically, how does poor water quality affect their efficiency?

Yves Desplenter: “Heat pump systems are more vulnerable to system water contamination than conventional boilers because they remove air less effectively when operating at low temperatures, although some heat pumps today also operate with high flow temperatures. You can easily be looking at a 25 to 40% loss in efficiency, compared with around 15% for conventional boilers.

And if the internal filters become clogged, the flow rate drops and the heat pump operates at only half capacity, while its COP (COP stands for coefficient of performance. It is a figure that indicates how efficiently a heat pump operates, ed.) plummets. Heat pump technology is excellent, but it is much more sensitive to water quality than conventional boilers. And replacing a boiler costs several times less than replacing a heat pump.”

Vincent Vancaeyzeele: “A 25 to 40% loss seems like a high estimate to me, but heat pump systems certainly lose more efficiency than conventional boilers when system water is contaminated.”

Pieterjan Spyns: “To clarify: more oxygen circulates in heat pumps because they remove air less effectively. This leads to more rust instead of magnetite, and rust is not magnetic, so conventional magnetic filters do not work.”

Pieterjan Spyns.

In renovation projects, heat pumps are often connected to old circuits. Does this pose an additional risk to system water quality?

Pieterjan Spyns: “Absolutely! You can be sure that old systems already contain contamination, have had leaks and have often been topped up many times. That means extra oxygen and deposits. So you are connecting sensitive technology to a contaminated past. You can already tell it is going to go wrong. That is why it is crucial to analyse and treat existing systems thoroughly before connecting a heat pump to them.” ‎‎

Who is responsible when a heating or cooling system underperforms because of poor system water quality?

Yves De Meuter: “You have to look at each case individually. There is rarely one clearly identifiable party at fault. In practice, the end user usually turns to the installer first. If the problem becomes more complex, the manufacturer gets involved, and in larger cases engineering consultancies, architects or the client also join the discussion.”

Vincent Vancaeyzeele: “In cases involving major damage, you often see a chain of blame, with everyone pointing the finger at someone else. Only in serious cases does it lead to legal proceedings, with an expert appointed.”

Yves Desplenter: “Residential cases are usually settled amicably.”

Vincent Vancaeyzeele: “I would like to stress that most heating and cooling systems are installed by passionate installers. Problems are often the result of a combination of circumstances.”

Yves De Meuter: “The customer may, for example, have done something that caused or exacerbated the problems, such as adding or draining water unnecessarily.”

Is system water quality adequately addressed in specifications today?

Pieterjan Spyns: “On private projects, no. It is virtually non-existent there. The subject does come up on larger projects, but often only superficially. As I said earlier, the technical knowledge needed is too often lacking.”

Vincent Vancaeyzeele: “You do see it more often on larger projects, but it is often limited to general wording such as ‘good workmanship’. The fact that guidelines are sometimes referred to does not mean much if people are unfamiliar with them.”

What treatment should be standard for system water in heating and cooling installations today?

Pieterjan Spyns: “Filling with demineralised or at least softened water. That is the starting point. It is also advisable to limit the amount of steel in low-temperature systems, check for contamination and pH levels, and prevent oxygen ingress by choosing the right materials. In practice, for example, we fill with demineralised water and add an inhibitor such as Fernox F1 to help prevent corrosion and limescale build-up over the long term.”

So, in practical terms, how do you monitor system water quality throughout the installation’s service life?

Yves Desplenter: “When the system is commissioned, the water quality should be measured, treated with inhibitors if necessary, and documented. This provides a benchmark. Periodic checks are then needed, comparing the values from a water sample with the original readings, with action taken when necessary.”

Pieterjan Spyns: “We systematically measure the pH and check the effectiveness of any inhibitors present, using Fernox test strips. This is particularly important if we did not install the system ourselves.”

Vincent Vancaeyzeele: “Everything Yves has mentioned should be standard, and we are repeating ourselves here, but it is not. In practice, water analysis is often the first thing to go when quotes are compared on price, or because neither the customer nor the designer has a clear grasp of its importance. In practice, as Pieterjan rightly does, we focus on parameters such as pH and inhibitors, but we rarely measure the decisive factor, oxygen, directly. The reason is that this is technically very difficult and requires very expensive measuring equipment, such as the kind used in the food industry.”

Pieterjan Spyns: “Prevention is always cheaper and easier. You can flush, clean and treat the system afterwards, but that takes more time, costs more money, and you can never guarantee that everything has been resolved”

Yves De Meuter.

What is the financial cost to users of poor water quality in a heating or cooling installation? Do you have any figures or practical examples?

Yves Desplenter: “That is difficult to quantify. You would have to add up the cost of interventions, how much extra energy you use and the price of gas or electricity at the time, what exactly needs replacing … To my knowledge, there are no reliable studies on this, either regionally or internationally.”

Vincent Vancaeyzeele: “If your installation lasts twenty years instead of twelve, you get eight extra years at lower cost. That is how you should look at it, I think.”

Yves De Meuter: “About two years ago, Europe scrapped a kind of assessment in this area, the audit of a heating installation. It focused on the actual performance of a heating system.”

Do manufacturers set specific system water quality requirements in their warranty terms? And what happens in practice when a warranty applies and an installation fails because of poor system water?

Yves De Meuter: “Manufacturers, including us at Vaillant Group, set clear requirements for pH, conductivity, hardness … But of course, we depend on the installer. When problems arise, a tailored solution is usually worked out. The manufacturer sometimes covers part of the cost, but there are limits.”

Yves Desplenter: “We are seeing a clear shift in this respect on larger installations: water analysis is carried out at commissioning, and there is regular follow-up recorded in a logbook. This is still done too rarely for smaller installations.”

Vincent Vancaeyzeele: “Warranty claims are not usually an issue in most cases. Most problems only arise after the two-year statutory warranty period has expired.”

Many end users see treating system water in heating or cooling installations as an extra cost. How do you explain it transparently without making people feel that something is being pushed on them?

Pieterjan Spyns: “I don’t sell anything, I explain. I try to make the importance as tangible as possible, using simple examples: a pan of water, two pieces of pipe, what happens with air and temperature. People can then see for themselves the difference between an installation where everything is right and one where it is not. Once you show them visually, the penny usually drops. The problem is that end users do not always get that explanation.”

Yves Desplenter: “Cost is not the problem. For an average installation, water treatment costs about 40 euros, out of a total of roughly 15,000 euros. That is negligible. The real problem is that many people simply underestimate the impact of water quality.”

I think that is indeed the most important conclusion from this round-table discussion. What could the installation sector do differently to improve system water quality in a lasting way?

Pieterjan Spyns: “Above all, the sector needs to understand that heating and cooling installations should not be filled with well water, mains water or rainwater, only treated water, in other words, demineralised or at least softened water. Manufacturers and installers should also use materials that help minimise problems with system water. These two approaches are inextricably linked. If you focus on only one of them, you will still have problems. Finally, installers need to make a point of emphasising the importance of system water quality to their customers.”

Yves De Meuter: “The authorities also have a role to play: if water quality were made a mandatory part of the handover of an installation, for example through a simple proof-of-compliance document, that would already be a major step forward. It would guarantee a minimum standard of quality.

In addition, greater awareness is needed not only among installers and end users, but among all the parties involved, including architects and engineering consultancies. In some cases, bringing in specialist companies to carry out analysis and follow-up can also add value, particularly for more complex installations.”

Vincent Vancaeyzeele: “End users, and to a lesser extent architects, pay little attention to building services when a construction project is being delivered. So there is a need for awareness-raising and legislative measures.”

Yves De Meuter: “I would add one caveat. Installers are being given more and more responsibilities. In the past, the focus was mainly on hydraulics; now there is electricity, controls and, increasingly, water chemistry too. The question is whether all of this is still manageable.”

Thank you for your valuable insights, gentlemen.

Question about this story? Ask your question

Companies in this story

Keep following this