News

Sint-Angelusinstituut, Sint-Lambrechts-Woluwe | Clean air in a new school building

Sint-Angelusinstituut, Sint-Lambrechts-Woluwe | Clean air in a new school building

Atelier M Architects + Planners was given the challenging task of designing a passive school building in collaboration with Ingenieursbureau BOTEC, which was responsible for the building services. The project follows the Educare concept and includes a nursery as well as a primary school, helping children make the transition from toddler to preschooler as smoothly as possible. 

The architects designed a compact building for 250 primary school pupils, 120 preschool children and 42 toddlers. A clear layout was achieved through a highly repetitive arrangement of classrooms and a rectilinear structure of large service risers running through the different floors. This architecture naturally lends itself to a clear layout of limited building services networks, running from the plant rooms on the roof or in the basement through the building’s insulated envelope.

Although passive construction is primarily a matter of insulation values and airtightness, the HVAC installation designed by BOTEC also played an important role in limiting heat loss. Both air-handling units were located in a plant room on the roof, within the insulated envelope. The main ducts from the service risers connect directly to this plant room, so air is not transported through the external environment.
Since the compact boiler room is on the roof and the showers are in the changing rooms in the basement, it made sense to produce the limited amount of domestic hot water locally, using an electric water heater. Overall, this produces domestic hot water much more efficiently than a circulating hot-water pipe that has to be kept constantly warm.

Next to the E40

Sint-Angelusinstituut is located right next to the E40, where passing traffic produces large quantities of particulate matter every day. Recent studies show that air quality in schools is poor and exceeds the maximum limits.

BOTEC’s design team took the following measures to provide the children with the cleanest possible air. The obvious choice was to ventilate the building using a balanced mechanical ventilation system (system D). As well as offering acoustic benefits, since a system C installation with window vents does not block out all ambient noise, this option also made it possible to use double filtration on the air intake side of the air-handling units. The filters to be installed meet the highest standards for filtering airborne particulate matter. It is also important to keep CO2 levels in classrooms within limits at all times, as occupancy can vary considerably when movable partitions are used. This was addressed by equipping each classroom with demand-controlled ventilation linked to a CO2 meter. BOTEC’s design offers two benefits. If CO2 levels rise in a classroom, a damper system (VAV box) in the ventilation network directs more air to that room, bringing CO2 levels back down. If a classroom is lightly occupied, CO2 levels will also be low, and the CO2 meter will signal to the damper system to reduce the airflow to the room. This allows the air-handling unit to run at a lower speed and use less energy. Larger spaces such as the dining hall, multi-purpose rooms and sports hall are also equipped with a damper system. This means the air-handling units operate according to occupancy. In effect, the air follows the pupils around the building. Since ventilation usually accounts for a large share of electricity consumption, this demand control will result in significant electricity savings. The entire system is monitored by a building management system, enabling remote management.

The same amount of light for all pupils, at any time of day

Thanks to the building’s simple structure and layout, the number of different LED light fittings is limited. This uniformity allows larger quantities of the same fittings to be purchased, reducing the cost and freeing up budget for the energy-efficient daylight dimming concept. Under this system, light fittings next to the windows switch off automatically when there is enough daylight, while those along the corridor side remain on.

Question about this story? Ask your question

Who worked on it

Sint-Angelusinstituut in Sint-Lambrechts-Woluwe

  1. architectAtelier M Architects + Planners
  2. techniquesIngenieursbureau BOTEC

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ProjectSint-Angelusinstituut
  • SubjectNews
  • CompanyAtelier M Architects + Planners
  • CompanyIngenieursbureau BOTEC
Share this article

Follow on Installatie & Bouw Vlaanderen

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.