Protect the heat pump from frost

Caleffi’s frost protection valve (series 108) automatically drains the pipes when the temperature approaches freezing, protecting the circuit against ice formation, which can cause frequent damage and faults in heat pumps.
The Caleffi frost protection valve (series 108) automatically drains the pipes when the temperature approaches freezing, protecting the circuit against ice formation, which can cause frequent damage and faults in heat pumps.
Monobloc system
In a heat pump system with a monobloc, the unit is located outdoors, so the pipes are also installed outside. This puts the entire installation at risk of freezing, so frost protection must be considered. Electric trace heating is often chosen, but the drawback is that it will not work during a power cut. A frost protection valve that automatically drains the pipes when there is a risk of freezing offers a solution.
How it works
When the integrated temperature sensor detects that the water temperature in the pipe has reached 3 °C, the thermostatic element in the frost protection valve opens the shutter and drains the pipes. This prevents potential damage to the heat pump and pipes. When the water temperature rises again, the valve closes.
Installation
To drain all the water from the pipes, frost protection valves are installed on both the flow and return pipes. They must always be installed vertically to ensure that the water drains correctly. Make sure there is at least 15 centimetres between the valve and the ground.
Install the frost protection valves on the section of pipe that reaches the lowest temperature when the heat pump is off. During installation, there must be no heat sources near the installation point that could affect the valves’ correct operation. The valve must never be insulated either.
For the valves to work correctly, the system must always remain pressurised, even when the valves are drained.
Additional benefits
Both the thermostatic element and the vacuum seal can be replaced if necessary, so there is no need to install a completely new valve. When replacing the thermostatic element, an automatic shut-off valve prevents water from escaping while the system remains pressurised.
As well as being compact and easy to install, series 108 requires little maintenance and is suitable for universal use. It can be installed in any heat pump system.
All in all, it is a small investment that can prevent much worse. Better safe than sorry….