Reliable CO2 measurement for energy-efficient ventilation

Accurate measurement with automatic self-calibration
We spend up to 90% of our lives indoors, so healthy indoor air is vital. That is why many HVAC systems are equipped with CO2 sensors. To ensure an adequate supply of fresh air without over-ventilating, these sensors need to remain stable over the long term. The new Belimo room sensors are designed to continue providing accurate CO2 measurements thanks to Dual Beam self-calibration. The result? Lower energy consumption, better air quality and greater comfort.
Poor indoor air quality can lead to health problems, difficulty concentrating and lower productivity. High CO2 concentrations are not synonymous with poor air quality, but they are a good indicator that more ventilation is needed. Demand-controlled ventilation with CO2 sensors is therefore the gold standard. Yoram Mottas, system engineer for sensor development at Belimo, talks enthusiastically about the new room sensors, which measure temperature, humidity and CO2 levels to control ventilation systems.

Stable CO2 measurement over the long term
“We developed our room sensors with a ‘non-dispersive infrared dual-channel detection element’. Put simply, they are equipped with a tiny measuring chamber containing a light source and two detectors. The light passing through the chamber is absorbed by CO2 molecules. One detector uses an infrared filter to register the reduction in light, while the other measures the unfiltered light intensity. The sensor compares the two measurements to determine the CO2 level,” explains Yoram Mottas.
“That Dual Beam design ensures accurate measurement over the long term. If the reference value were to drift as the IR beam ages, the measured value could be adjusted proportionally.
That is why Belimo CO2 sensors are suitable for all types of buildings, including those where air quality is critical or occupancy is 24/7, such as classrooms, hospitals, logistics centres and factories. We have made our room sensors extremely robust, so they continue to measure with great precision, without external calibration.”
Accurate under all conditions
Belimo room sensors also measure accurately under all conditions. “Did you know that the pressure difference at 400 metres above sea level already causes a deviation of 70 ppm in the measured CO2 concentration? That is why our room sensors feature absolute pressure compensation to neutralise pressure differences,” says Yoram Mottas.
“To ensure our sensors operate reliably at all times and in all places, we tested them for weeks under highly demanding conditions. For example, we tested their corrosion resistance at a relative humidity of 95% and a temperature of 35 °C, as well as the materials’ coefficient of expansion at temperatures of up to 70 °C. All sensor elements are also designed to keep self-heating to a minimum.”

Energy-efficient demand-controlled zone ventilation
Zone ventilation usually follows a set sequence and is based on preset CO2 levels. Belimo room sensors communicate directly with the variable air volume (VAV) actuators on the supply air dampers. This enables the ventilation system to operate fully on demand, based on accurate measurements. As a result, fresh air is supplied only when it is really needed, preventing unnecessary energy consumption while ensuring air quality and comfort.
Thanks to NRC communication, installers, engineers and building managers can commission the sensors, check and adjust settings and parameters, and read measurements on their smartphones using the Belimo Assistant App. Users can operate the sensors without a display using the Belimo Display App. The solution also integrates seamlessly with all common building automation and control systems (BACS).
Een zakelijke vraag aan BELIMO Belgium bv? Get in touch
Companies in this story
Keep following this
Get an email when a new story is published. No account needed.
- ThemeHealthy air and summer comfort
- SubjectVentilation
- CompanyBELIMO Belgium bv